Manufacturing
How a power transformer is built.
Scroll to assemble a three-phase oil-immersed power transformer, from the bare core to a tested unit. Scroll back up to take it apart.
Scroll to build it
- 01 / 08
Core
Grain-oriented silicon-steel laminations are cut to length and stacked with step-lap joints to keep no-load loss and noise low. The top yoke is then unlaced so the windings can be lowered onto the limbs.
- Material
- Grain-oriented silicon steel
- Joints
- Step-lap, mitred
- Equipment
- Soenen cut-to-length line
- 02 / 08
Windings
Each limb takes a low-voltage winding next to the core and a high-voltage winding outside it, separated by pressboard cylinders and spacers. The top yoke is re-laced and the active part is clamped.
- Arrangement
- Concentric: LV inner, HV outer
- HV coils
- 20 t horizontal winding machine
- LV coils
- Foil winding machine
- 03 / 08
Leads and tap changer
Winding ends are connected to the bushing leads, and tapping leads run to the tap changer: on-load (OLTC) for regulation in service, or off-circuit (OCTC) for settings chosen at commissioning.
- HV leads
- To HV bushings
- LV leads
- Copper bar, incl. neutral
- Tap changer
- OLTC or OCTC
- 04 / 08
Vacuum drying
The active part is heated under vacuum to draw moisture out of the cellulose insulation. It is re-clamped afterwards, because the insulation shrinks as it dries.
- Removes
- Moisture from paper and pressboard
- Then
- Re-clamping of the windings
- 05 / 08
Tank, cover and bushings
The dried active part goes into the welded tank without delay, the cover is bolted on and the high- and low-voltage bushings are mounted on it.
- Tank
- Robot-welded steel
- HV bushings
- 3 phases
- LV bushings
- 3 phases + neutral
- 06 / 08
Oil filling
Filtered, degassed insulating liquid is filled under vacuum so that no air stays trapped in the insulation, followed by a standing time before testing.
- Liquid
- Mineral oil or natural ester
- Method
- Filling under vacuum
- 07 / 08
Cooling and conservator
Radiators carry heat away by natural oil and air circulation (ONAN); fans add forced air (ONAF). The conservator takes up oil expansion, with a Buchholz relay and breather on its pipework.
- Cooling
- ONAN, ONAF with fans
- Protection
- Buchholz relay
- Breathing
- Silica-gel breather
- 08 / 08
Tests and release
Routine tests confirm every unit before shipment: ratio and vector group, winding resistance, no-load and load loss, impedance, applied and induced voltage, and partial discharge. Lightning impulse and temperature rise are added when specified.
- Lightning impulse
- 2,400 kV test system
- Power frequency
- 300 kV test system
- Partial discharge
- 8-channel detector
Where each step happens at Tianyu.
The same sequence runs through the Fuzhou manufacturing base, from core cutting and winding lines to the test laboratory.